ISM Guidelines for communications infrastructure controls (2026)

The ISM Guidelines for communications infrastructure domain has 53 controls. This page lists every one, in plain language, with what it asks of you and the kind of evidence that actually satisfies it. The Australian Government Information Security Manual, the control set IRAP assessments use.

By Aneis Samaan, founder of CyberSentien · Last updated November 2026 · Sourced from the ISM control set.

What the Guidelines for communications infrastructure domain covers

These 53 controls are the Guidelines for communications infrastructure slice of ISM. Read them as the questions an assessor will ask, and the artefacts you will be asked to produce for each. Below every control we keep the language of the source; the value we add is turning each into an evidence question you can answer honestly.

The 53 controls in ISM Guidelines for communications infrastructure

ControlWhat it requires
ism-0181Cabling infrastructure is installed in accordance with relevant Australian Standards, as directed by the Australian Communications and Media Authority.
ism-0187SECRET cables, when bundled together or run in conduit, are run exclusively in their own individual cable bundle or conduit.
ism-0194In shared facilities, a visible smear of conduit glue is used to seal all plastic conduit joints and TOP SECRET conduits connected by threaded lock nuts.
ism-0195In shared facilities, uniquely identifiable SCEC-approved tamper-evident seals are used to seal all removable covers on TOP SECRET cable reticulation systems.
ism-0198When penetrating a TOP SECRET audio secure room, the Australian Security Intelligence Organisation is consulted and all directions provided are complied with.
ism-0201Labels for TOP SECRET conduits are a minimum size of 2.5 cm x 1 cm, attached at five-metre intervals and marked as ‘TS RUN’.
ism-0206Cable labelling processes, and supporting cable labelling procedures, are developed, implemented and maintained.
ism-0208A cable register contains the following for each cable: - cable identifier - cable colour - sensitivity/classification - source - destination - location - seal numbers (if applicable).
ism-0211A cable register is developed, implemented, maintained and regularly verified.
ism-0213SECRET and TOP SECRET cables are terminated on their own individual patch panels.
ism-0216TOP SECRET patch panels are installed in individual TOP SECRET cabinets.
ism-0217Where spatial constraints demand non-TOP SECRET patch panels be installed in the same cabinet as a TOP SECRET patch panel: - a physical barrier in the cabinet is provided to separate patch panels - only personnel holding a Positive Vetting security clearance have access to the cabinet - approval from the TOP SECRET system’s authorising officer is obtained prior to installation.
ism-0218If TOP SECRET fibre-optic fly leads exceeding five metres in length are used to connect wall outlet boxes to IT equipment, they are run in a protective and easily inspected pathway that is clearly labelled at the IT equipment end with the wall outlet box’s identifier.
ism-0246When an emanation security risk assessment is required, it is sought as early as possible in a system’s life cycle.
ism-0249System owners deploying SECRET or TOP SECRET systems in mobile platforms, or as a deployable capability, contact ASD for an emanation security risk assessment.
ism-0250IT equipment meets industry and government standards relating to electromagnetic interference/electromagnetic compatibility.
ism-0926Non-classified, OFFICIAL: Sensitive and PROTECTED cables are coloured neither salmon pink nor red.
ism-1095Wall outlet boxes denote the systems, cable identifiers and wall outlet box identifier.
ism-1096Cables are labelled at each end with sufficient source and destination details to enable the physical identification and inspection of the cable.
ism-1098SECRET cables are terminated in an individual cabinet; or for small systems, a cabinet with a division plate between any SECRET cables and non-SECRET cables.
ism-1100TOP SECRET cables are terminated in an individual TOP SECRET cabinet.
ism-1101In TOP SECRET areas, cable reticulation systems leading into cabinets in server rooms or communications rooms are terminated as close as possible to the cabinet.
ism-1102Cable reticulation systems leading into cabinets are terminated as close as possible to the cabinet.
ism-1103In TOP SECRET areas, cable reticulation systems leading into cabinets not in server rooms or communications rooms are terminated at the boundary of the cabinet.
ism-1105SECRET and TOP SECRET wall outlet boxes contain exclusively SECRET or TOP SECRET cables.
ism-1107Non-classified, OFFICIAL: Sensitive and PROTECTED wall outlet boxes are coloured neither salmon pink nor red.
ism-1109Wall outlet box covers are clear plastic.
ism-1111Fibre-optic cables are used for cabling infrastructure instead of copper cables.
ism-1112Cables in non-TOP SECRET areas are inspectable every five metres or less.
ism-1114Cable bundles or conduits sharing a common cable reticulation system have a dividing partition or visible gap between each cable bundle and conduit.
ism-1115Cables from cable trays to wall outlet boxes are run in flexible or plastic conduit.
ism-1116A visible gap exists between TOP SECRET cabinets and non-TOP SECRET cabinets.
ism-1119Cables in TOP SECRET areas are fully inspectable for their entire length.
ism-1122Where wall penetrations exit a TOP SECRET area into a lower classified area, TOP SECRET cables are encased in conduit with all gaps between the TOP SECRET conduit and the wall filled with an appropriate sealing compound.
ism-1123A power distribution board with a feed from an Uninterruptible Power Supply is used to power all TOP SECRET IT equipment.
ism-1130In shared facilities, cables are run in an enclosed cable reticulation system.
ism-1133In shared facilities, TOP SECRET cables are not run in party walls.
ism-1137System owners deploying SECRET or TOP SECRET systems within fixed facilities contact ASD for an emanation security risk assessment.
ism-1164In shared facilities, conduits or the front covers of ducts, cable trays in floors and ceilings, and associated fittings are clear plastic.
ism-1216SECRET and TOP SECRET cables with non-conformant cable colouring are banded with the appropriate colour and labelled at inspection points.
ism-1639Building management cables are labelled with their purpose in black writing on a yellow background, with a minimum size of 2.5 cm x 1 cm, and attached at five-metre intervals.
ism-1640Cables for foreign systems installed in Australian facilities are labelled at inspection points.
ism-1645Floor plan diagrams are developed, implemented, maintained and regularly verified.
ism-1646Floor plan diagrams contain the following: - cable paths (including ingress and egress points between floors) - cable reticulation system and conduit paths - floor concentration boxes - wall outlet boxes - network cabinets.
ism-1718SECRET cables are coloured salmon pink.
ism-1719TOP SECRET cables are coloured red.
ism-1720SECRET wall outlet boxes are coloured salmon pink.
ism-1721TOP SECRET wall outlet boxes are coloured red.
ism-1820Cables for individual systems use a consistent colour.
ism-1821TOP SECRET cables, when bundled together or run in conduit, are run exclusively in their own individual cable bundle or conduit.
ism-1822Wall outlet boxes for individual systems use a consistent colour.
ism-1884Emanation security doctrine produced by ASD for the management of emanation security matters is complied with.
ism-1885Recommended actions contained within emanation security mitigation advice issued for systems are implemented by system owners.

The false-green trap in this domain

The failure mode is the same in every framework: a control marked ‘compliant’ with nothing behind it. An assertion is not evidence. For each control above, the honest test is whether you can point to a dated, specific artefact — a configuration export, a log extract, a signed policy, a register entry — not a claim that you ‘do that’. That is exactly what CyberSentien enforces: a control with no evidence reads manual assessment required, never a fabricated pass. How the engine assesses →

Assess once, report everywhere

You do not answer to one framework in isolation. The same body of evidence maps across everything you are accountable to — which is the whole point of assessing once against real evidence and reporting everywhere. Related on this site:

Frequently asked questions

How many controls are in the ISM Guidelines for communications infrastructure domain?

There are 53 controls in this domain of ISM. They are all listed above with what each requires.

What evidence satisfies these controls?

Evidence is specific and dated: configuration exports, logs, signed policies, register entries and test results tied to the control, not a written assertion that the control exists. CyberSentien refuses to mark a control compliant without that lineage.

Does CyberSentien assess ISM?

Yes. ISM is one of the frameworks live on the CyberSentien engine, assessed against your real evidence with honest coverage and tamper-evident report lineage.

Every capability referenced on this page is live on the CyberSentien engine — see it on the always-live gated demo. Nothing on this page is legal advice.