The New Zealand Information Security Manual 10. Infrastructure — 10.4. Cable Management for Shared Non-Government Facilities domain has 19 controls. This page lists every one, in plain language, with what it asks of you and the kind of evidence that actually satisfies it. New Zealand Information Security Manual (NZISM) v3.9.
By Aneis Samaan, founder of CyberSentien · Last updated November 2026 · Sourced from the New Zealand Information Security Manual control set.
These 19 controls are the 10. Infrastructure — 10.4. Cable Management for Shared Non-Government Facilities slice of New Zealand Information Security Manual. Read them as the questions an assessor will ask, and the artefacts you will be asked to produce for each. Below every control we keep the language of the source; the value we add is turning each into an evidence question you can answer honestly.
| Control | What it requires |
|---|---|
NZISM-10.4.4.C.01 | NZISM 10.4.4.C.01 — Use of fibre optic cabling (MUST; Top Secret) In TOP SECRET areas, agencies MUST use fibre optic cabling. |
NZISM-10.4.4.C.02 | NZISM 10.4.4.C.02 — Use of fibre optic cabling (SHOULD; All Classifications) Agencies SHOULD use fibre optic cabling. |
NZISM-10.4.5.C.01 | NZISM 10.4.5.C.01 — Cabling inspection (MUST; Top Secret) In TOP SECRET areas, cables MUST be fully inspectable for their entire length. |
NZISM-10.4.5.C.02 | NZISM 10.4.5.C.02 — Cabling inspection (SHOULD; All Classifications) Cabling SHOULD be inspectable at a minimum of five-metre intervals. |
NZISM-10.4.6.C.01 | NZISM 10.4.6.C.01 — Cables sharing a common reticulation system (MUST; Top Secret) In TOP SECRET areas, approved cable groups can share a common reticulation system but MUST have either a dividing partition or a visible gap between the differing cable groups. |
NZISM-10.4.6.C.02 | NZISM 10.4.6.C.02 — Cables sharing a common reticulation system (MUST; Top Secret) TOP SECRET cabling MUST run in a non-shared, enclosed reticulation system. |
NZISM-10.4.6.C.03 | NZISM 10.4.6.C.03 — Cables sharing a common reticulation system (SHOULD; All Classifications) Approved cable groups can share a common reticulation system but SHOULD have either a dividing partition or a visible gap between the differing cable groups. |
NZISM-10.4.7.C.01 | NZISM 10.4.7.C.01 — Enclosed cable reticulation systems (MUST; Top Secret) In TOP SECRET areas, the front covers for conduits and cable trays in floors, ceilings and of associated fittings MUST be clear plastic or be inspectable and have tamper proof seals fitted. |
NZISM-10.4.7.C.02 | NZISM 10.4.7.C.02 — Enclosed cable reticulation systems (SHOULD; All Classifications) The front covers of conduits, ducts and cable trays in floors, ceilings and of associated fittings SHOULD be clear plastic or be inspectable and have tamper proof seals fitted. |
NZISM-10.4.8.C.01 | NZISM 10.4.8.C.01 — Cabling in walls or party walls (MUST NOT; Confidential, Secret, Top Secret) Cabling MUST NOT run in a party wall. |
NZISM-10.4.9.C.01 | NZISM 10.4.9.C.01 — Sealing reticulation systems (MUST; Top Secret) Agencies MUST use GCSB endorsed tamper evident seals to seal all removable covers on reticulation systems, including: conduit inspection boxes; outlet and junction boxes; and T-pieces. |
NZISM-10.4.9.C.02 | NZISM 10.4.9.C.02 — Sealing reticulation systems (MUST; Top Secret) Tamper evident seals MUST be uniquely identifiable and a register kept of their unique number and location. |
NZISM-10.4.9.C.03 | NZISM 10.4.9.C.03 — Sealing reticulation systems (MUST; Top Secret) Conduit joints MUST be sealed with glue or sealant. |
NZISM-10.4.9.C.04 | NZISM 10.4.9.C.04 — Sealing reticulation systems (SHOULD; All Classifications) Conduit joints SHOULD be sealed with glue or sealant. |
NZISM-10.4.10.C.01 | NZISM 10.4.10.C.01 — Wall penetrations (MUST; Secret, Top Secret, Confidential) Wall penetrations that exit into a lower classified area, cabling MUST be encased in conduit with all gaps between the conduit and the wall filled with an appropriate sealing compound. |
NZISM-10.4.11.C.01 | NZISM 10.4.11.C.01 — Power reticulation (MUST; Confidential, Top Secret, Secret) Secure facilities MUST have a power distribution board located within the secure area and supply UPS power all equipment. |
NZISM-10.4.12.C.01 | NZISM 10.4.12.C.01 — Power Filters (MUST; Top Secret, Secret, Confidential) Power filters MUST be used to provide filtered (clean) power and reduce opportunity for technical attacks. |
NZISM-10.4.13.C.01 | NZISM 10.4.13.C.01 — Equipment Cabinet separation (MUST; Confidential, Secret, Top Secret) Equipment cabinets MUST have a visible gap or non-conductive isolator between cabinets of different classifications. |
NZISM-10.4.13.C.02 | NZISM 10.4.13.C.02 — Equipment Cabinet separation (SHOULD; All Classifications) There SHOULD be a visible inspectable gap or non-conductive isolator between equipment cabinets of different classifications. |
The failure mode is the same in every framework: a control marked ‘compliant’ with nothing behind it. An assertion is not evidence. For each control above, the honest test is whether you can point to a dated, specific artefact — a configuration export, a log extract, a signed policy, a register entry — not a claim that you ‘do that’. That is exactly what CyberSentien enforces: a control with no evidence reads manual assessment required, never a fabricated pass. How the engine assesses →
You do not answer to one framework in isolation. The same body of evidence maps across everything you are accountable to — which is the whole point of assessing once against real evidence and reporting everywhere. Related on this site:
There are 19 controls in this domain of New Zealand Information Security Manual. They are all listed above with what each requires.